Safe distance to be paid attention to when arranging the interior of industrial gas steam boiler roo

The net distance of the front end of the whole industrial gas steam boiler should not be less than 2 �� 3 of the furnace body length, and not less than 2 meters, and the vertical industrial gas steam boiler can be properly shortened. Bulk industrial gas steam boiler is not less than 4 meters, and does not affect the operation and maintenance before the furnace.

Safe distance to be paid attention to when arranging the interior of industrial gas steam boiler roo

2. The net distance between the side and back of the industrial gas steam boiler should not be less than 0.8 meters, and it should meet the requirements of operation and maintenance (such as changing pipe bundles, cleaning ash, dialing fire, etc.).

3. The clearance height at the top of horizontal industrial gas steam boiler shall not be less than 2m;The clearance height on the top of vertical industrial gas steam boiler shall be convenient for operation and maintenance;The clearance height of other channels of industrial gas steam boiler room shall not be less than 2m. When operation and passage is not required, the clearance height shall be 0.7m.

4. For industrial gas steam boiler rooms with two or more industrial gas steam boilers, the distance between adjacent industrial gas steam boilers should not be less than 1 to 1.5 times the diameter of industrial gas steam boilers.

5. The industrial gas steam boiler room should generally be set up as the operating room of the furnace worker. For a hot water industrial gas steam boiler with a fixed evaporation capacity greater than or equal to 4t/h (or a hot water industrial gas steam boiler with a heat supply greater than or equal to 2.8MW), the operating room of the company must be set up. The electric control box of industrial gas steam boiler can also be located in front of industrial gas steam boiler, and ensure that the personnel of the company can face the water level meter, pressure meter and other instruments of industrial gas steam boiler.

6. the total rated evaporation is greater than 2t/h fuel. Foam fire extinguishers or water spray systems should be installed in gas industry gas steam boiler rooms, outdoor fire hydrants should be installed, and other industrial gas steam boiler rooms should also have fire extinguishing equipment.

7. in the daily fuel tank of the fuel industry gas steam boiler room, the oil pump should not be located in the industrial gas steam boiler room, the daily fuel tank room, and the partition wall with the fire resistance limit greater than 2.00h should be used between the oil pumps. The floor with fire resistance limit greater than 1.50h is separated from other parts. The doors between fuel tank and oil pump in industrial gas steam boiler room should be Class A fire doors which can be closed automatically, and oil blocking measures should be set up. The upper part of the daily fuel tank should be returned to the tubing, and the return oil should be greater than the oil pump.

8. The oil storage tank and all pipelines must have reliable electrostatic grounding, and the grounding resistance should not be greater than 30 ohms.

9. The design scheme of gas steam boiler room in gas industry shall also comply with relevant safety technical requirements of gas steam boiler room of gas industry.