The phenomenon of diesel fired steam boiler full water level
(1) the water level meter can't see the water level, the color inside the glass tube (plate) of the water level meter is dimmed,
(2) the double color water level meter of the boiler shows all the water phase indication color; (3) the high water level alarm signal occurs in the boiler high and low water level alarms,
(3) the superheated steam temperature of the boiler obviously drops, (5) the feed water flow rate of the diesel fired steam boiler is abnormal larger than the steam flow rate; (6) when the boiler is full of water, a large amount of water is stored and the water drain is violent; (7) when the boiler is full of water, a large amount of steam is brought with water, the salt content is increased, the sound of water hammer occurs in the steam pipe, and the water drips out of the flange;
2, causes of full boiler water (1) Boiler personnel neglect to monitor the water level, (2) the valve of boiler feed water automatic regulation is not normal, resulting in a large amount of feed water to the boiler; (3) the steam and water connected pipe of boiler water table meter block and discharge cock leak, cause water level indication not correct, cause operation error.
3, diesel fired steam boiler full water treatment method: (1) flushing first and proofreading the water level of each water level meter, (3) the boiler full water treatment method: (1) flushing and checking the water level of each water level meter first, To determine the authenticity of the water level indication. If the water level is still visible, the water level is slightly full; if the water level is not visible, it should be; call the water method to determine whether the water is slightly full or seriously full of water. Fill the water; the way to call water is as follows: (1) wash the water table once in the normal order; (2) rinse After completion, close the cock on the water level meter and water pipe;
4. open the blow-and-wash cock. If the water level is seen falling from the top of the glass tube (plate), it can be concluded that it is slightly full of water, and if the water level is not visible, the whole glass tube (plate) can only see the water flow downward. It can be concluded that the boiler is seriously full of water. (2) if the diesel fired steam boiler is slightly full of water. The following treatment methods should be adopted: (1) to adjust the combustion intensity to make the combustion weaken; (2) to stop the feed water and open the drain valve to discharge water; 3 until the water level is normal, close all discharge valves and return to normal operation.
(3) if the boiler is seriously full of water, the following treatment methods should be adopted: 1. Emergency shutdown program shut down; 2 stop feed water, strengthen sewage valve discharge; 3 open steam main pipe and superheater water delivery valve for rapid water delivery; 4 after normal water level, close the sewage valve and each drain valve, and then resume the operation of rising fire.