1. The door of the industrial gas steam boiler room leading to the outside should be opened outward. There should be at least two exits on each floor of the industrial gas steam boiler room, each of which shall be located on both sides. When the total width of the front end of the industrial gas steam boiler (including the aisle between the industrial gas steam boilers) does not exceed 12 m, and the area of the industrial gas steam boiler room does not exceed 200m2, only one outlet can be opened.
2. The door of the industrial gas steam boiler room shall not adopt a moving door or a rolling curtain door pulled up and down. The height and width of the main door of the industrial gas steam boiler room with rated evaporation less than or equal to 2t/h industrial gas steam boiler should not be less than the maximum assembly size of the industrial gas steam boiler plus 0.5 m.
3. The ground of industrial gas steam boiler room should be flat, no steps and no water accumulation, and the lower drainage hole (ditch) should be opened on the ground of industrial gas steam boiler room to facilitate drainage.
4. The construction of industrial gas steam boiler room shall comply with the requirements of Code for Fire Protection of Buildings and the Code for Fire Protection of High-rise Civil Buildings.
5. The wall of industrial gas steam boiler (less than 1.5 meters from the ground) should adopt moisture-proof measures such as cement plaster or tile veneer, and wash it with water.
6. The operation place in the industrial gas steam boiler room, as well as the water level meter, pressure gauge, thermometer, flow meter, etc., shall be provided with sufficient lighting.
7. The industrial gas steam boiler arranged in the open air shall be provided with operation room, and the measurement and control instruments such as the water level of the industrial gas steam boiler and the pressure of the industrial gas steam boiler shall be centralized in the operation room, and the industrial gas steam boiler and the safety accessories shall be provided with reliable rain-proof, wind-proof and anti-freezing. Anti-corrosion measures.
8. For industrial gas steam boilers with no fire-proof partition walls in the wood production workshop, the firewall shall be built with non-combustible body and the fire-resistant limit of 4h. The firewall shall be directly built on the foundation or the frame of reinforced concrete. The firewall shall cut off the roof structure of the combustible or difficult-combustible body, and shall be 400mm higher than the roof of the non-combustible body and 500mm higher than the roof of the combustible body or the combustible body.